Honeywell Gas Valve Actuator, V4055E1016

Honeywell Gas Valve Actuator, V4055E1016
Code: ACT-V4055E1016
Price: $588.27
Quantity in Basket: None
Quantity:
Manufacturer: Honeywell

V4055A, B, D, E On-Off Fluid Power Gas Valve Actuator

The V4055 Gas Valve Actuator, in combination with a VE5000a, V5055 or V5097 Gas Valve, controls the gas supply to commercial and industrial burners. When replacing a V4034 with a V4055, the V5034 gas valve must also be replaced with a V5055 or V5097 gas valve.

Features
• The V4055 Actuator, when used with the VE5000¹, V5097 or V5055 Valve, is rated for final safety shutoff service.
• The V4055 Actuator can be used with the characterized guide model of the V5055 or V5097 Gas Valve to enhance lightoff smoothness.
• The standard model has an opening time of 26 seconds at 60 Hz or 32 seconds at 50 Hz. A fast-opening model is available with timings of 13 seconds at 60 Hz or 16 seconds at 50 Hz.
• Maximum closing time is one second, which meets code, standard and insurer requirements.
• Models available with damper shaft, with or without spring return; shaft extends out both sides and rides in Teflon-like Delrin bushings; used with standard 7616BR Damper Crank Arm.
• Red OPEN indicator attached to actuator stem shows when valve is even slightly open; yellow SHUT indicator on valve stem shows only when gas valve is fully closed.
• Models available with adjustable max flow limit switch.
• Ambient temperature rating is -40°F to +150°F (-40°C to +66°C) for 60 Hz models and -10°F to +158°F (-23°C to +70°C) for 50 Hz and 50/60 Hz models.
• Valve and actuator combinations can be mounted in any position, with the exception of the 220 to 240 Vac, 50/60 Hz models, which are mounted vertically.
• Models available with factory-installed single pole double throw (spdt) field-adjustable Auxiliary Switch. Field-addable Auxiliary Switch kits are also available.
• Standard enclosure meets NEMA 1 (IP30) requirements; models available with NEMA 4 (IP54) weatherproof enclosure.
• V4055D and high pressure V4055E with Proof-of-Closure Switch and V5055/V5097C or E with valve seal overtravel interlock (double seal) to meet specific code, standard and insurer requirements.

¹VE5000 is a European manufactured and approved valve for European use only.

Specifications
Models:
• V4055A Actuator, with V5055, V5097 or VE5000 Gas Valves, provides on-off control of fuel. With proper adapter (see Accessories), it replaces the V4034 Actuator on a V5034 Gas Valve.
• V4055B Actuator is a high pressure version of V4055A.
• V4055D Actuator is identical to V4055A, except has a Proof-of-Closure Switch. Used with V5055C/V5097C (double seal) for valve seal over-travel interlock.
• V4055E Actuator is identical to V4055B, except has a Proof-of-Closure Switch. Used with V5055E/V5097E (double seal) for valve seal over-travel interlock.
• NEMA 4 weatherproof models available.

Nominal Opening Time (seconds)
Model
50 Hz
60 Hz
Standard
32
26
Fast-opening
16
13

Maximum Closing Time: One second when de-energized.
Ambient Operating Temperature Ratings:
• 60 Hz Models: -40°F to 150°F (-40°C to 66°C)
• 50 Hz, 50/60 Hz Models: -10°F to 158°F (-23°C to 70°C)
Mounting: V4055 Actuator attaches directly to V5055/V5097 Valve with two sets of screws positioned 90-degrees apart. Combination is multipoise.
NOTE: 220-240 Vac, 50/60 Hz models are vertical mount only.

Pressure Ratings of Valve-Actuator Combinations
Valve
V4055A, D¹
V4055B, E¹
Differential²
Closeoff³
Differential²
Closeoff³
psi
mbar
psi
bar
psi
mbar
psi
bar
V5055/V5097 A, C: 3/4  to 3 in.
5
340
15
1
15
1000
15
1
V5055A, C: 4 in.
3
200
15
1
5
340
15
1
V5055/V5097B: 3/4 to 3 in.
5
340
15
1
15
1000
15
1
V5055B: 4 in.
3
200
15
1
5
340
15
1
V5055/V5097D,E: 3/4, 1-1/4, 1-1/2 in.
5
340
75
5
25
1700
75
5
V5055/V5097D,e: 2, 2-1/2, 3 in.
5
340
45
3
15
1000
45
3
¹ Use a V4055D or V4055E (with Proof-of-Closure Switch) with a V5055/V5097C or V5055/V5097E (with double seal) for valve seal overtravel interlock.
² Maximum operating pressure differential.
³ Maximum closeoff pressure without seat leakage. This is the maximum valve pressure drop allowed while fully closed, and is independent of the valve body rating.

V4055A, D Electrical Ratings
Voltage and Frequency
Opening (Standard)
Opening (Fast)
Holding
Inrush
(W)
(A)
(VA)
Inrush
(W)
(A)
(VA)
(W)
(A)
(VA)
100/50-60¹ --
43.0
0.91
91
--
58.0
1.30
130
10.4
0.16
16
100/50-60² --
33.0
0.6
67
--
43.0
0.91
91
8.4
0.14
14
120/60
3.9
50.0
0.94
115
5.4
71.0
1.33
160
9.5
0.12
14
200/50-60¹ --
68.0
0.79
158
--
88.0
1.10
220
10.6
0.09
18
200/50-60² --
48.0
0.52
104
--
63.0
0.72
144
9.0
0.07
14
220/50
1.6
55.5
0.55
121
3.0
76.0
0.80
176
9.0
0.06
14
240/50
--
81.5
0.79
190
--
95.0
1.00
240
9.1
0.06
14
240/60
2.6
51.0
0.45
115
4.0
71.5
0.68
160
9.2
0.06
14
220-240/50-60³ --
--
--
--
--
70.3
0.59
136
7.2
0.07
16
220-240/50-60⁴
--
--
--
--
--
58.6
0.46
106
5.9
0.06
14
¹ 50 Hz power supply
² 60 Hz power supply
³ 230 Vac, 50 Hz power supply
⁴ 230 Vac, 60 Hz power supply

V4055B, E Electrical Ratings
Voltage and Frequency
Opening (Standard)
Opening (Fast)
Holding
Inrush
(W)
(A)
(VA)
Inrush
(W)
(A)
(VA)
(W)
(A)
(VA)
120/60
--
60
0.94
115
--
60.0
0.94
115
9.5
0.16
19
220-240/50-60
--
--
--
--
--
68.9
0.58
133
6.7
0.08
18
220-240/50-60
--
--
--
--
--
58.2
0.46
106
5.3
0.06
14

Replaces Part Number: V4055E1016

XMN

CF