Honeywell Diaphragm Gas Valve, V88A1675

Honeywell Diaphragm Gas Valve, V88A1675
Code: GAS-V88A1675
Price: $216.57
Quantity in Basket: None
Quantity:
Manufacturer: Honeywell

V48A, F, J; V88A, J Diaphragm Gas Valve

The V48 and V88 are solenoid-operated diaphragm valves suitable for LP (Liquefied Petroleum), natural, and manufactured gases. They are normally used on atmospheric boilers, commercial water heaters, and rooftop heaters.

Features

• Line voltage, 2-wire thermostat or controller used with a V48; V88 used with 24V thermostat
• Valves provide slow opening and fast closing
• Two second maximum closing time
• V48J, V88J rated for 150F (66C) ambient temperature
• V48F rated for 5 psi (34.5 kPa). V48A and V88A rated for either 1/2 or 1 psi (3.4 or 6.9 kPa), depending on model. V48J and V88J rated for 1 psi (6.9 kPa)
• One model for natural and LP gases
• Wide range of sizes and capacities
• Firm closing; diaphragm is both weight and spring loaded
• Valve closes on power failure; recommended for final shutoff service
• Adjustable or fixed bleed orifices available for installation by OEM
• Valve position indicator on 1-1/4 in. V48A2227 and 2 in. V48F1103 Valves

Specifications
Models:
• V48A (120 Vac) or V88A (24 Vac) solenoid operated diaphragm valves for 1/2 or 1 psi (3.4 or 6.9 kPa) maximum operating pressure.
• V48F (120 Vac) solenoid operated diaphragm valve for 5 psi (34.5 kPa) maximum operating pressure.
• V48J (120 Vac) or V88J (24 Vac) solenoid operated diaphragm valves for 1 psi (6.9 kPa) operating pressure and 150°F maximum ambient temperature.

Type of Gas: Suitable for liquefied petroleum (LP), natural, manufactured, and sulfur-bearing gases.

Valve Pattern: Straight-through, non-offset.

Valve Body Material: Die-cast aluminum.

Pilot Tapping:
• 3/4 through 1-1/2 inch valves: 1/8-27 NPT or 1/8-28 BSP.PI
• 2 through 3 inch valves: 1/4-18 NPT.

Bleed Tapping: 1/8-27 NPT or 1/8-28 BSP.PI.

Valve Opening Time:
Five seconds maximum at 2 oz/in.2 (0.86 kPa) pressure. Adjustable bleed valve assembly or fixed bleed orifices available for longer opening time (NPT threads only)

Valve Closing Time (on power failure; measured at 2 oz/in.2 [0.86 kPa] pressure): 2 seconds maximum.

Power Consumption (maximum): 9 watts or 15 VA.

Ambient Temperature Rating:
• V48A,F and V88A: 32°F to 125°F (0°C to 52°C).
• V48J and V88J: 32°F to 150°F (0°C to 66°C).

Maximum Fluid Temperature:
• V48A,F; V88A: 125°F (52°C).
• V48J; V88J: 150°F (66°C).

Thermostat Heat Anticipator Setting: For 60 Hz V88, set at 0.6A.

Optional Feature: Valve position indicator is available on 1-1/4 in. V48A2227 and 2 in. V48F1103.
Replacement Coil Assemblies:¹
• 116930: 24V, 60 Hz V88A
• 116931: 120V, 60 Hz V48A.
• 116932: 220V, 50 Hz V48A
• 116932: 240V, 60 Hz V48A
• 118888: 24V, 60 Hz V88J
• 139937: 120V, 60 Hz V48J

¹ These V48/V88 bonnet assemblies and solenoid operators are not compatible with old style valve bodies.

Replaces Part Number: V88A1675

XMN

CF