High Limit; Manual Reset Aquastat Controller with 100 F to 240 F operating temperature and 66 in. ca

High Limit; Manual Reset Aquastat Controller with 100 F to 240 F operating temperature and 66 in. ca
Code: aqt-4008E1313
Price: $198.78
Quantity in Basket: None
Quantity:

Product Description

Overview
For limiting or regulating temperature of liquids in boilers or tanks. Can also sense duct or outside air temperature.

Features
• Remote temperature sensing element detects and responds rapidly to temperature changes.
• Totally enclosed Micro Switch™ snap-acting switch.
• Visible control point scale and external adjustment screw permit easy setting.
• Horizontal or vertical mounting of the remote element into boiler, tank, or other container.
• Case mounts to a vertical surface.

Product Specifications
Description High Limit; Manual Reset Aquastat Controller with 100 F to 240 F operating temperature and 66 in. capillary
Application High Limit; Manual Reset
Bulb Size (in.) 3/8 in. x 2 7/8 in. copper
Bulb Size (mm) 10 mm x 73 mm copper
Capillary Length (in.) 66 in.
Switching Action SPST, contacts break on temperature rise.
Operating Temperature Range (F) 100 F to 200 F
Operating Temperature Range (C) 38 C to 116 C
Electrical Ratings (millivolt) 0.25 A @ 0.25 to 12 Vdc
Electrical Ratings (AFL) 8A @ 120 Vac
Electrical Ratings (AFL) 5.1A @ 240 Vac
Electrical Ratings (ALR) 48A @ 120 Vac
Electrical Ratings (ALR) 30.6A @ 240 Vac
Differential Temperature (F) Manual Reset
Differential Temperature (C) Manual Reset
Maximum Ambient Temperature (F) 150 F
Maximum Ambient Temperature (C) 66 C
Case Dimensions (in.) 5 5/8 in. high x 2 in. wide x 2 1/8 in. deep
Case Dimensions (mm) 143 mm high x 51 mm wide x 54 mm deep
Mounting Horizontal or Vertical
Approvals, Underwriters Laboratories Inc UL Component Recognized: File No. MP466, Vol. 6, Sec.1, Guide No. MBPR2
Approvals, Canadian Standards Association Certified: File No. LR95329-1

Replaces Part Numbers:
AASL4088E1313 l4088E1313


CF